Armoured low-voltage power cable 0.6/1 kV, copper conductors, PVC insulated, round steel wire armour, PVC sheathed. 2 to 5 cores, sizes from 1.5 to 240 mm².
Cu/PVC/SWA/PVC (NYRY – YVZ2V)
Power cable 0.6/1 kV with Cu conductors, PVC insulated, round steel wire armour and PVC sheathed
Locations under mechanical stress, underground, in power and switching stations, industrial plants.
| Conductors | Class 1 or class 2 acc. to IEC 60228 |
| Insulation | PVC compound |
| Bedding | Extruded elastomer compound |
| Armour | Round steel wire |
| Sheath | PVC compound |
| CPR class | Eca |
| Rated voltage | 0.6/1 kV |
| Bending radius | 15D / 12D |
| Max. conductor temperature | 70°C |
| Max. short-circuit temperature | 160°C |
| Standard | IEC 60502-1 |
| Core identification | According to HD 308 S2 |
| 2 core | Brown – Blue |
| 3 core | Brown – Black – Grey |
| 4 core | Blue – Brown – Black – Grey |
| 5 core | Green/Yellow – Blue – Brown – Black – Grey |
| Sheath colour | Black (other colours available) |
Two core cables
| Cross-section mm² | Max. resistance at 20°C Ω/km | Outer dia. (approx.) mm | Weight (approx.) kg/km | Current capacity in earth A | Current capacity in air A |
|---|---|---|---|---|---|
| 2x1.5 | 12.1 | 12.5 | 320 | 32 | 22 |
| 2x2.5 | 7.41 | 13.3 | 375 | 42 | 30 |
| 2x4 | 4.61 | 15.0 | 475 | 54 | 40 |
| 2x6 | 3.08 | 16.9 | 660 | 68 | 51 |
| 2x10 | 1.83 | 19.4 | 870 | 90 | 70 |
| 2x16 | 1.15 | 21.5 | 1085 | 116 | 94 |
| 2x25 | 0.727 | 25.5 | 1620 | 150 | 119 |
Three core cables
| Cross-section mm² | Max. resistance at 20°C Ω/km | Outer dia. (approx.) mm | Weight (approx.) kg/km | Current capacity in earth A | Current capacity in air A |
|---|---|---|---|---|---|
| 3x1.5 | 12.1 | 13 | 355 | 27 | 19 |
| 3x2.5 | 7.41 | 13.8 | 415 | 36 | 25 |
| 3x4 | 4.61 | 15.7 | 540 | 47 | 34 |
| 3x6 | 3.08 | 17.7 | 740 | 59 | 43 |
| 3x10 | 1.83 | 20.4 | 995 | 79 | 59 |
| 3x16 | 1.15 | 22.6 | 1270 | 102 | 79 |
| 3x25 | 0.727 | 26.9 | 1910 | 133 | 106 |
| 3x35 | 0.524 | 29.3 | 2330 | 159 | 129 |
| 3x50 | 0.387 | 33.2 | 2955 | 188 | 157 |
| 3x70 | 0.268 | 37.8 | 4090 | 232 | 199 |
| 3x95 | 0.193 | 43.0 | 5275 | 280 | 246 |
| 3x120 | 0.153 | 46.2 | 6275 | 318 | 285 |
| 3x150 | 0.124 | 51.9 | 8015 | 359 | 326 |
| 3x185 | 0.0991 | 57.5 | 9725 | 406 | 374 |
| 3x240 | 0.0754 | 64.3 | 12275 | 473 | 445 |
Four core cables
| Cross-section mm² | Max. resistance at 20°C Ω/km | Outer dia. (approx.) mm | Weight (approx.) kg/km | Current capacity in earth A | Current capacity in air A |
|---|---|---|---|---|---|
| 4x1.5 | 12.1 | 13.7 | 395 | 27 | 19 |
| 4x2.5 | 7.41 | 14.7 | 470 | 36 | 25 |
| 4x4 | 4.61 | 17.7 | 730 | 47 | 34 |
| 4x6 | 3.08 | 18.9 | 860 | 59 | 43 |
| 4x10 | 1.83 | 22.1 | 1170 | 79 | 59 |
| 4x16 | 1.15 | 25.3 | 1650 | 102 | 79 |
| 4x25 | 0.727 | 29.2 | 2270 | 133 | 106 |
| 4x35 | 0.524 | 32.0 | 2810 | 159 | 129 |
| 4x50 | 0.387 | 37.5 | 3870 | 188 | 157 |
| 4x70 | 0.268 | 41.3 | 4960 | 232 | 199 |
| 4x95 | 0.193 | 48.3 | 6890 | 280 | 246 |
| 4x120 | 0.153 | 52.5 | 8220 | 318 | 285 |
| 4x150 | 0.124 | 57.0 | 9775 | 359 | 326 |
| 4x185 | 0.0991 | 63.6 | 12010 | 406 | 374 |
| 4x240 | 0.0754 | 70.8 | 15160 | 473 | 445 |
Five core cables
| Cross-section mm² | Max. resistance at 20°C Ω/km | Outer dia. (approx.) mm | Weight (approx.) kg/km | Current capacity in earth A | Current capacity in air A |
|---|---|---|---|---|---|
| 5x1.5 | 12.1 | 14.6 | 450 | 19 | 14 |
| 5x2.5 | 7.41 | 15.6 | 545 | 25 | 19 |
| 5x4 | 4.61 | 18.8 | 835 | 33 | 26 |
| 5x6 | 3.08 | 20.4 | 1005 | 41 | 32 |
| 5x10 | 1.83 | 24.7 | 1535 | 55 | 44 |
| 5x16 | 1.15 | 27.4 | 1960 | 71 | 59 |
| 5x25 | 0.727 | 31.8 | 2670 | 93 | 80 |
| 5x35 | 0.524 | 35.7 | 3560 | 111 | 97 |
| 5x50 | 0.387 | 40.6 | 4540 | 132 | 118 |